Garbage Trolley Rectification- The Galleries (JB004-26-01406)
Break Down
Mixed Use
Meydan, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Garbage Trolley Rectification- The GalleriesOuter door rubber damaged—4Nos • Need to replaceTrolley need outer door rubber with fixing accessories---Trolley No,4Note: Kindly visit the site before submitting the quotation and verify scope of work
Proposal for Programming of Unprogrammed Capacitor Bank (JB004-26-01403)
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Executive Summary:
The capacitor banks installed across Jewellery & Gemplex Buildings 1, 2, and 3 are currently unprogrammed and have not been properly commissioned, rendering them operationally inactive in terms of power factor correction and electrical efficiency management. Each building is equipped with four capacitor...
Proposal for repair and replacement of damaged shaft door (JB004-26-01397)
Break Down
Mixed Use
Atlantic Tower, Dubai Marina, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
At Atlantic Building – Tower 1, 4th floor, the fire riser shaft access door has been found severely damaged, with issues such as dents, misalignment, and faulty hinges. This condition poses safety risks and affects operational reliability. Immediate repair or replacement is required to restore safe and secure access.Conduct a...
Proposal for Rectification of Scrubber system (JB004-26-01385)
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Currently, 6
out of the 9 units are non-operational due to damage caused by chemical exposure.
The failure of these systems has disrupted building operations, as smoke accumulation has resulted in
violations of environmental standards. This situation presents significant risks to public health and
compromises the safety an...
Replacement of defective pressure vessel bladder (JB004-26-01278)
Break Down
Residential
The Spirit, Dubai Sports City, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Replacement of defective pressure vessel bladderUpon detailed inspection, the following was observed: • The internal bladder (membrane) of the pressure vessel is damaged/ruptured. • Air and water are no longer properly separated inside the vessel. • The vessel has lost its ability to maintain required pressure ...
Break Down
Residential
The Spirit, Dubai Sports City, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
The domestic water pipeline system in Spirit Tower has multiple rusted and defective gate valves, PRVs, and PPR fittings across various floor locations as follows :Ground floor1st floor Aside1st floor Bside6th floor Aside6th floor Bside7th floor Bside8th floor Aside8th floor Bside14th floor16th floor Aside16th floor Bside17th...
Break Down
Residential
JVT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Isolation of power supply to ensure safe working.
Removal of damaged FCU motor (1 No.).
Rewinding of motor winding.
Reinstallation of motor after rewinding.
Testing and commissioning of FCU unit.
Final checking to ensure proper operation.
Mechanical Electrical Plumbing (MEP) Break Down (JB1099-26-01353)
Break Down
Residential
Dubai Land, Dubai, United Arab Emirates
Posted By: SG Community Management Services LLC
Dear
Service Provider,
Greetings from Strata Global!
We
kindly invite you to do a site visit and send us your proposal for the Rooftop
Exhaust Duct Modification Works in Etlala 2 located
in Wadi Al Safa 5, Dubailand
Scope
of Works:
For site visit and
clarifications, p...
Break Down
Mixed Use
Al Shera Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Comprehensive Replacement of Chilled Water Pipe Insulation System Basement to RooftopThe purpose of this contract is to appoint a qualified contractor to undertake the complete survey, engineering assessment, removal, supply, installation, testing, and commissioning of a high-performance chilled water pipe insulation system a...
Break Down
Residential
The Spirit, Dubai Sports City, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
The building’s DEWA water meter rooms and associated common areas are experiencing recurring water
leakage incidents due to the severe corrosion and deterioration of water pipes, fittings, and valves. The aging
infrastructure has compromised the integrity of the water supply system, resulting in uncontrolled water
discharg...
Main MCCB Power Tripping (JB004-26-01091)
Break Down
Mixed Use
Dubai Marina, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Main MCCB Power Tripping Faulty 63A MCCB to be isolated safely. • Existing damaged MCCB to be removed. • Supply lines to be checked and tightened before replacement. • Install new 63A MCCB of approved specification. • Phase balancing and voltage testing to be carried out after installation.&nbs...
Proposal for Rewinding of FCU Motor – Zazen One (JB004-26-01016)
Break Down
Residential
JVT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Scope of Work:
Inspection of the affected FCU unit serving the 4th floor corridor.
Dismantling and removal of the damaged FCU motor.
Rewinding of motor winding to restore operational condition.
Reinstallation of the motor and reconnection of power supply.
Testing and commissioning of the FCU to ensure proper functio...
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Summary
The chlorine dosing pumps serving the domestic water systems in J&G Buildings 1 and 3 are nonfunctional, resulting in the absence of required chemical treatment and disinfection. This presents a significant health, operational, and compliance risk, including potential bacterial growth, biofouling, and deterioratio...
No proper access for FCU (JB004-26-00974)
Break Down
Mixed Use
Tamweel Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
No proper access for FCUArrange adequate access for FCU PPM across all floors to prevent equipment damage and maintain efficiency
Drain line design deficiencies are causing leakage (JB004-26-00973)
Break Down
Mixed Use
Tamweel Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Drain line design deficiencies are causing intermittent leakageDue to a design flaw in the drain lines, there is leakage and odor in the apartment and common areas, posing
potential health risks to tenantsImproving the drain line design and performing the necessary repairs will completely eliminate the leakage and odor issues...
defective pressure vessel bladder (JB004-26-00972)
Break Down
Mixed Use
Tamweel Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
defective pressure vessel bladderReplace the defective pressure vessel bladder in CHW Make-up Tank (ETS B1) to restore and maintain proper system water
pressure.
Break Down
Mixed Use
Tamweel Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Isolator in the control panel of the CHW Make-up Pump System (ETS & Roof Panel) is defectiveReplace the defective isolator in the control panel of the CHW Make-up Pump System (ETS & Roof Panel) to ensure that power
can be safely disconnected, eliminating operational and safety risks
Water Leakage from CHW pipe Insulation (JB004-26-00967)
Break Down
Mixed Use
Tamweel Tower, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Water Leakage from chill water pipe Insulation Water seepage damaging followings,
Exit lights,
Fire alarm systems,
Gypsum ceilings,
Possible to damage CCTV camera.Replacing of CHW insulation from: (Total -335 Running meter approx.)
1) Removal of existing Insulation for Chilled water ...
Booster Pump No. 3, impeller body leakage (JB004-26-00965)
Break Down
Mixed Use
Goldcrest Views, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Booster Pump No. 3, impeller body leakage• Isolated and safely shut down Booster Pump No. 3. • Identified the exact leakage point on the impeller body • Replaced the damaged impeller
Proposal for Renovation Works – Main Garbage Room (JB004-26-00955)
Break Down
Mixed Use
IT Plaza, Dubai Silicon Oasis, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Summary
The main garbage room at the Ground Floor requires renovation due to extensive damage to floor and wall tiles, along with non-functional drainage and electrical systems caused by ageing components. The condition of the room has led to hygiene concerns, moisture infiltration, and operational inefficiencies.
Scope of Wo...
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Summary
Out of thirty (30 Nos.) Staircase Pressurization Fans (SPF) and Smoke Extract Fans (SEF) installed in 2004 across Jewellery & Gemplex Buildings 1, 2, and 3, nineteen (19 Nos.) units (sixteen (16 Nos.) SPF and three (3 Nos.) SEF) are currently non-operational. These systems are critical components of the building’s...
Proposal for Replacement of Variable Frequency Drives (JB004-26-00923)
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Proposal for Replacement of Variable Frequency Drives:Isolate and remove four (4) faulty 55 kW Schneider Electric VFD units from chilled water pump system.Supply four (4) new 55 kW VFDs compatible with existing pump motors.Install and reconnect power and control wiring.Program and configure VFD parameters as per motor require...
Break Down
Mixed Use
JLT, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Proposal for Replacement of Chemical Dosing Pump:The chilled water Chemical dosing pumps in all three buildings have been non-functional for an extended
period. As a result, no routine chemical dosing has occurred, which has likely led to degraded water quality
and an increased risk of corrosion and scaling within the chill...
Water leakage from ceiling. CHW pipeline insulation damaged (JB004-26-00874)
Break Down
Mixed Use
Goldcrest Views, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Water leakage from common area ceiling. CHW pipeline insulation damaged.Rectification and replacement of damaged CHW pipeline insulation. Cutting of ceiling sections where access is not available for insulation works.
Removal of ceiling portions damaged due to water leakage from the CHW pipelines.
Re-fixin...
CPVC flange T and Elbow failure (JB004-26-00873)
Break Down
Mixed Use
Goldcrest Views, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
CPVC flange T and Elbow failure Water leakage observed during routine inspection
Leakage identified at the CPVC flange connection
Crack detected in the CPVC T-joint
CPVC elbow found damaged and unsuitable for continued useReplace damaged CPVC components:
CPVC flange with gasket (4 bolts) – 75 mm ×...
replacing the Pressure Reducing Valve (JB004-26-00870)
Break Down
Mixed Use
Goldcrest Views, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
replacing the Pressure Reducing Valve PRVs (2½” size) QTY 32 • Replacement of faulty PRVs and butterfly valves is recommended to prevent further damage. Note: Please do the site visit before submitting the quotation.
AC Vibration and Noice Issue (JB004-26-00850)
Break Down
Residential
Pantheon Boulevard, Jumeirah Village Circle, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
A total of 16 outdoor AC units is installed on the rooftop area vibration and noise levels.Scope of Work: Carry out preventive maintenance and complete fan motor inspection and servicing for all 16 AC units
at the earliest to reduce vibration and noise levels and to ensure smooth and efficient operation. • The exist...
Break Down
Mixed Use
Goldcrest Views, Jumeirah Lakes Towers, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Mechanical room Booster pump pressure vessel line leak and Rubber flexible joint crack
at discharge line. During routine inspection, we found that the water leak at Pressure vessel old MS line which is
connected to discharge header of booster pump in Mechanical room. On further investigation, we found minute crack at R...
RECTIFICATION OF HOT WATER LEAKAGE (JB004-26-00227)
Break Down
Residential
The Diamond Tower, Dubai Sports City, Dubai, United Arab Emirates
Posted By: HOAM- Highrise Owners Association Management
Scope of Work – Hot Water Leak Rectification
Replacement of faulty gate valve and associated pipes in front of Apartment 1005.
Replacement of faulty PPR pipe, gate valve, and fittings, including ceiling repair and painting, in front of Apartment 609.
Replacement of PPR pipe and fittings in front of Apartment 209.
Apar...