QUOTATION REQUEST FOR RECTIFICATION OF SMOKE MANAGEMENT SYSTEM PROJECT

Break Down
Posted On: February 7, 2025
Closing On: April 15, 2025
JOB REFERENCE:
JB6873-25-00018

Scope of Work for Rectification of Smoke Management System

1. Fire-Rated Mechanical Works:

  • Remove existing fire-rated GI ductwork sealants and gaskets for:

    • (2) Staircase Pressurization Fans

    • (1) Makeup Fan at Mechanical Floor

  • Replace with new fire-rated gaskets and sealants.

  • Apply 2-hour fire-rated painting for Staircase and Lobby Pressurization ducts inside the shaft, including:

    • (1) Coat of red oxide primer

    • (1) Coat of fire-rated paint (1632 Sq.mts)

  • Supply and install:

    • Non-Return Dampers (NRD) for Staircase and Lobby Pressurization Fans

    • Motorized Dampers (MD) for Staircase and Lobby Pressurization Fans

    • Motorized Fire Dampers (MFD) for each Pressurization Fan

    • Pressure Release Dampers (PRD) for each Pressurization Fan

  • Electrical works:

    • Install new electrical connections for (2) MFDs

    • Repair existing electrical faults

  • Fire alarm interfacing:

    • Supply and install containment and cables for (2) MFDs and (3) MDs

2. Civil Works:

  • Construct concrete/block walls around MFD at Mechanical Floor (2 Nos.)

  • Create and seal wall openings in shaft for:

    • Duct access inside shafts, including plaster and painting

    • Installation of PRD (2 Nos.)

  • Apply fire-rated sealant around:

    • MFD and PRD

    • Leaks around ducts inside shafts

    • MSFD (Lobby Pressurization Motorized Smoke Fire Damper) inside each corridor

General Requirements:

  • Contractor must adhere to all relevant fire safety regulations and standards.

  • Work schedule to be coordinated with the facility management team.

  • Proper waste disposal and site cleaning upon completion of work.

  • Provide necessary certifications and compliance documentation upon completion.

Please contact Mr. Malik at 0525195078 for site visit scheduling. 
Terms & Condition

As per Dubai Land Department - Real Estate Regulatory Agency (RERA)
We are not authorized to pay advance under any circumstances. The payment will be 100% upon Completion.

APPLY NOW
SABA PROPERTY MANAGEMENT DMCC
SABA PROPERTY MANAGEMENT DMCC
SABA 3
SABA 3
Mixed Use

Cluster Q , Jumeirah Lakes Towers , Dubai, United Arab Emirates

Share