Supply and Installation of Electrical Insulating Rubber Mats

Enhancement
Posted On: November 4, 2025
Closing On: November 9, 2025
JOB REFERENCE:
JB007-25-04594

Dunya Tower - Ground Floor_ LV Room


Scope Of Work:

1. Supply

  • Provide insulating rubber mats rated for safe use in LV switchgear rooms, suitable for personnel standing in front of live or potentially live equipment.
  • Mat characteristics:
    • Minimum thickness: 3 mm (or as specified).
    • Surface finish: ribbed or anti-slip.
    • Width: minimum 1 m, and extend at least 1 m beyond the total width of each LV panel section.
  • Mats shall carry permanent markings including: class/rating, manufacturer name, batch/lot number, voltage rating.
  • Provide product datasheet and material compliance certificate for review/approval prior to installation.
  • Ensure materials comply with DEWA’s requirement for equipment and materials: all equipment and materials shall be selected in accordance with “Standards for equipment and materials” in DEWA’s Regulations for Electrical Installations.

2. Preparation

  • Inspect the LV room floor area: verify floor is dry, level, structurally sound, free of oil/grease, debris, sharp edges or protrusions.
  • Confirm that the layout of mats is coordinated with the client/consultant and aligns with the switchgear arrangement.
  • Provide or review layout drawing showing the mat arrangement in front of each panel for client/consultant approval.
  • Carry-out any floor repair, cleaning or priming necessary so that mat adhesion (if required) is effective.

3. Installation

  • Roll out and place the insulating mats in front of the LV switchgear/MCC panels ensuring full coverage of the designated zone.
  • Ensure mats lie flat, with no folds, wrinkles, bulges or gaps. Overlap joints if required using manufacturer-approved method.
  • Fix mats to prevent slipping – using non-conductive adhesive or mechanical edge strips as specified by the mat manufacturer.
  • Ensure all markings remain visible after installation.
  • Ensure installation is done without damage (cuts, punctures) to the mats; rectify any defects prior to testing.
  • Confirm that workmanship is “neat, orderly and in a workmanlike manner”, consistent with DEWA’s workmanship requirement.

4. Inspection & Testing

  • Conduct visual inspection: verify alignment, coverage, condition, and visible markings.
  • Where required by project specification, perform dielectric (insulation) test of the mats or verify that manufacturer’s test certificates apply.
  • Prepare and submit an installation completion report including: photos of installed mats, compliance certificates.
  • Coordinate with site FM team for final inspection and approval.
Warranty- 3 Years

 

 

Terms & Condition

No Subcontracting: In accordance to Jointly Owned Property Law No.6,2019, Notwithstanding anything in this Agreement, the vendor/contractor may not use any subcontractor to perform any of his obligations under this work order. Unless: 

(a) Vendor has obtained the prior written consent of SAGA to the use of the subcontractor, and 

(b) Vendor has entered into a separate written agreement with the subcontractor which requires the subcontractor to agree to and abide by all the terms and conditions of this Agreement. 

The Community shall be deemed to be a third-party beneficiary of any such agreement between the vendor and a permitted subcontractor. 

Notwithstanding the foregoing, the vendor shall not be relieved of any of its duties or obligations under this Agreement as a result of entering into a written agreement with a permitted subcontractor.