Inspection and Testing of Earth Pits

Compliance
Posted On: November 18, 2025
Closing On: November 22, 2025
JOB REFERENCE:
JB007-25-04736

1. Measurement of Earth Resistance

  • Perform earth resistance measurement for each earth pit using a calibrated digital earth tester.
  • Use the 3-point or 4-point method in accordance with IS/IEC standards (e.g., IS 3043).
  • Record readings under stable soil and weather conditions to ensure accuracy.

2. Testing of All Existing Earth Pits

  • Conduct testing on all identified and accessible earth pits within the premises.
  • Ensure compliance with relevant electrical safety and earthing standards.
  • Verify that each pit undergoes proper resistance measurement.

3. Physical Inspection & Verification

  • Inspect the physical condition of each earth pit, including:
    • Pit chamber structure.
    • Earthing electrode exposure.
    • Moisture condition and backfill.
  • Check connection integrity, including:
    • Condition of clamps and termination hardware.
    • Tightness and corrosion status of conductors.
    • Continuity of earth strips/wires.
  • Ensure all components meet required safety and quality norms.

4. Preparation of Earth Test Report

  • Prepare a detailed report containing:
    • Pit number / identification tag
    • Location of each earth pit
    • Measured earth resistance value (ohms)
    • Environmental conditions during testing
    • Visual inspection observations
  • Provide a summary sheet covering all pits tested.

5. Recommendations & Corrective Actions

  • Compare measured values with permissible limits recommended by applicable standards.
  • Provide recommendations for improvement where resistance values are higher than allowable limits.
  • Suggest corrective measures such as:
    • Soil enhancement
    • Addition of chemical compound
    • Re-tightening / replacement of clamps
    • Conductor replacement
    • Installation of parallel earth electrodes (if required)

6. Minor Rectification Work

  • Perform minor corrective actions on-site, including:
    • Cleaning and tightening of clamps and connections.
    • Removal of corrosion from conductor joints.
    • Top-up of water or backfill compounds (if necessary).
    • Ensuring pit covers are properly seated and labeled.
  • Report any major defects that require additional work beyond this scope.

 

Terms & Condition

No Subcontracting: In accordance to Jointly Owned Property Law No.6,2019, Notwithstanding anything in this Agreement, the vendor/contractor may not use any subcontractor to perform any of his obligations under this work order. Unless: 

(a) Vendor has obtained the prior written consent of SAGA to the use of the subcontractor, and 

(b) Vendor has entered into a separate written agreement with the subcontractor which requires the subcontractor to agree to and abide by all the terms and conditions of this Agreement. 

The Community shall be deemed to be a third-party beneficiary of any such agreement between the vendor and a permitted subcontractor. 

Notwithstanding the foregoing, the vendor shall not be relieved of any of its duties or obligations under this Agreement as a result of entering into a written agreement with a permitted subcontractor.