Chiller#1 Compressor & Parts Replacement
ProductJOB REFERENCE:
JB007-25-04571
Ch-1: Parts and Compressor Replacement
Model: YCIV1000
Serial No: RKSM020008 – System 1
Scope of Work:
· Isolate the chiller from electrical source.
· Recover the refrigerant from the system.
· Supply and replacement of compressor for circuit#1.
· Pressure test the system to identify and repair the
leak.
· Evacuate system as per standards.
· Supply and replacement of drier core and oil filter.
· Supply and replacement of oil.
· Charge back the recovered refrigerant and top-up (up
to 65 kgs).
· Supply and replacement of IGBT Board.
· Supply and replacement of suction temperature sensor
of circuit-1.
· Supply and replacement of entering & leaving
temperature sensor.
· Supply and replacement of IGBT Snubber.
· Remove the defective capacitors.
· Supply and replacement of VSD capacitors &
laminated bus plate.
· Repair/rewinding and fix back condenser fan motor.
· Start-up the chiller and observe the operation and
log parameters.
· Hand over the chiller to the customer.
DESCRIPTION QTY
MTS45 COMPRESSOR 1
OIL FILTER WITH ORING 1
DRIER CORES 2
OIL L TYPE 5 GALLON 1
NITROGEN 2
R134-A 13.6KG 5
IGBT BOARD 1
SUCTION TEMPERATURE SENSOR 1
FAN MOTOR REPAIR 1
VSD CAPACITOR 6
LAMINATED BUS PLATE 1
ENTERING & LEAVING WATER TEMPERATURE SENSOR 2
IGBT SNUBBER 3
LABOR CHARGES LOT
All work/inspection must be completed in comply with site requirements and to follow the safety procedures. All work relevant pre-schedule documents like Work Method statement, Risk Assessment, valid supporting documents, insurance documents etc., to be provided for necessary approval from client appointed FM service provider/safety officer.
Terms & Condition

SAGA International Owners Association Management Services LLC

Dorra Bay Tower Jointly Owned Property
ResidentialDorra Bay Tower Dubai Marina, Dubai, United Arab Emirates