UPS AMC
Contract
Posted On:
December 26, 2024
Closing On:
December 29, 2024
JOB REFERENCE:
JB6913-24-00068
DESCRIPTION
1 KVA – 5 Nos
4 KVA – 2 Nos QTY 01
6 KVA – 6 Nos
20 KVA – 1 Nos
SCOPE OF WORK
Quarterly Maintenance Service (4 times per year)
Check the UPS Panel display by stimulating the fault and observe if there is any alarm
Check the ambient temperatures and humidity.
Cleanliness of UPS Power module
Cleanliness of control panel
Inspect proper operation of cooling fan/Ventilation fan of the UPS
Inspect all ac capacitors for signs of leakage
Check Electricals connections and internal protection fuses
Cleanliness of UPS power module
Checking incoming DC voltage /current/frequency all phase
Checking Rectifier input voltage /current/frequency all phase
Checking incoming Dc voltage and current
Checking the UPS for Normal, Battery and bypass operation
Check system output voltages /current/ frequency all phase
Check system bypass voltage /current /frequency all phase
Check the load percentage
General appearance of battery system
Check battery current, voltage, Continuity, Charging & Discharging Status
Inspect the battery terminals keep the cleaned and free of corrosion replace as needed
Submission of Service maintenance log sheet/report.
FREQUENCY
Quarterly Maintenance Service (4 times per year)
DURATION OF CONTRACT
1st JAN ,2025 TO 31st DEC .2025